Boiler Water Tank

Short Description:

Boiler Water Tank used for keeping the boiler water


Product Detail

Used in Boiler

Tank accessories
(1) Water inlet pipe: The water inlet pipe of the water tank is generally connected from the side wall, but it can also be connected from the bottom or top.
When the water tank USES the pipe network pressure to fill the water, the inlet pipe outlet should be equipped with a floating ball valve or hydraulic valve.
Generally, there are not less than 2 floating ball valves.
The diameter of the ball float valve is the same as that of the inlet pipe, and each ball float valve shall be equipped with an inspection valve before it.
(2) Outlet pipe: the outlet pipe of the water tank can be connected from the side wall or the bottom.
The bottom of the outlet pipe connected from the side wall or the top surface of the outlet pipe connected from the bottom shall be 50 mm higher than the bottom of the water tank.
The outlet pipe shall be equipped with gate valve.
The inlet and outlet pipes of the water tank should be set separately. When the inlet and outlet pipes are the same pipe, check valve should be installed on the outlet pipe.
When it is necessary to install check valves, swing check valves with less resistance should be used instead of lifting check valves, and the elevation should be more than 1m below the lowest water level of the water tank.
When a water tank is used jointly by life and fire control, the check valve on the fire control outlet pipe should be lower than the pipe top of the domestic water outflow siphon (when the vacuum of the domestic siphon is destroyed when the water is lower than the pipe top, only the water flow out of the fire control outlet pipe is guaranteed at least 2M, so that it has a certain pressure to push the check valve.
When a fire occurs, the fire water reserve can really play a role.
(3) Overflow pipe: the overflow pipe of the water tank can be connected out from the side wall or the bottom, and its pipe diameter shall be determined according to the maximum inlet flow of the discharge tank, and shall be larger than the intake pipe L-2.
Valves shall not be installed on the overflow pipe.
The overflow pipe shall not be directly connected with the drainage system, and indirect drainage shall be adopted. Measures shall be taken on the overflow pipe to prevent the entry of dust, insects, mosquitoes and flies, such as water seal and filter screen, etc.
(4) Drain pipe: the water tank drain pipe should be connected from the lowest part of the bottom.
Drain pipe Figure 2-2N The water tank for fire fighting and living table is equipped with a gate valve (should not be equipped with a cut-off valve), which can be connected with the overflow pipe, but not directly connected with the drainage system.
Drainage pipe diameter generally adopts DN50 when there is no special requirement.
(5) Ventilation pipe: The water tank for drinking water shall be provided with a sealed box cover, and the box cover shall be provided with access hole and ventilation pipe.
Ventilation pipe can be extended to indoor or outdoor, but not to harmful gases. The nozzle should have a filter screen to prevent dust, insects and flies from entering. Generally, the nozzle should be set down.
Ventilation pipe shall not be equipped with valves, water seals and other devices that interfere with ventilation.
Ventilation pipe shall not be connected with drainage system and ventilation duct.
Ventilation pipe generally adopts the diameter of DN50.
(6) Liquid level meter: Generally, glass liquid level meter should be installed on the side wall of the water tank to indicate the water level on the spot.
When the length of one liquid level gauge is insufficient, two or more liquid level gauges can be installed up and down.
The overlap part of two adjacent liquid level gauges should not be less than 70mm, as shown in Figure 2-22.
If there is no liquid level signal timing in the water tank, signal tube can be set to give the overflow signal.
The signal tube is generally connected from the side wall of the water tank, and its height should be set so that the bottom of the tube is level with the bottom of the overflow tube or the overflow water surface of the flared mouth.
Generally, the diameter of the pipe is DNl5 signal pipe, which can be connected to the washbasin, washing basin and other places in the room where there are often people on duty.
If the level of the water tank is interlocked with the water pump, the level relay or signal device shall be installed on the side wall or top cover of the water tank. The commonly used level relay or signal device includes float ball type, pole type, capacitance type and float type, etc.
The high and low electric hanging water level of the water tank with water pump pressure should be considered to maintain a certain safe volume. The maximum electric control water level at the moment of stopping the pump should be 100 mm lower than the overflow water level, while the minimum electric control water level at the moment of starting the pump should be 20mm higher than the design minimum water level, so as to avoid overflow or cavitation caused by error.
(7) Water tank cover, internal and external ladder.
BOILER WATER TANK

  • Previous:
  • Next:

  • Write your message here and send it to us

    Related products

    • Double Drum Steam Boiler

      Double Drum Steam Boiler

      Coal Steam Boiler-Used in Foods, Textile, Plywood,Paper Brewery,Rice Mill etc.. Introduction : SZL Series assembled water tube boiler adopts longitudinal double drum chain grate boiler. The boiler body is composed of up& down longitudinal drums and convection tube, best heating surface, high thermal efficiency, reasonable design, compact structure, elegant appearance, adequate effect. Two side of Combustion chamber equipped the light pipe water wall tube, up drum equip steam ...

    • Biomass Steam Boiler

      Biomass Steam Boiler

      Biomass Boiler-Hot Sale- Easy Installation Low Heating Value Fuel Wood Rice Husk Pellets etc. Introduction : Biomass Steam Boiler is horizontal three-back water fire pipe composite boiler. Fix fire tube in drum and the light pipe water wall is fixed on the right and left sides of the furnace. With light chain grate stoker for mechanical feeding and by the draft fan and blower for mechanical ventilation, realize mechanical taphole by scraper slag remover. The hopper of fuel drops to ...

    • Gas Steam Boiler

      Gas Steam Boiler

      Introduction : WNS series steam boiler burning oil or gas is Horizontal internal combustion three backhaul fire tube boiler, adopts boiler furnace wet back structure, high temperature smoke, gas turn to scour the second and third backhaul smoke tube plate, then after the smoke chamber. discharged into the atmosphere through the chimney. There are the front and back Smokebox Cap in the boiler, easy to maintenance. Excellent burner adopts combustion automatic ratio adjustment , feedwater ...

    • Single Drum Steam Boiler

      Single Drum Steam Boiler

      Introduction : Single Drum Chain Grate Coal fired boiler is horizontal three-back water fire pipe composite boiler. Fix fire tube in drum and the light pipe water wall is fixed on the right and left sides of the furnace. With light chain grate stoker for mechanical feeding and by the draft fan and blower for mechanical ventilation, realize mechanical taphole by scraper slag remover. The hopper of fuel drops to grate bar, then enter furnace for burning, by the ashes room above the back arch, t...