Parameter :
DZG(L)Bearing Pressure Hot water boiler
Main Technology Parameter List
Model | DZG0.7-0.7/95/70 DZL0.7-0.7/95/70 |
DZG1.4-0.7/95/70 DZL1.4-0.7/95/70 DZL1.4-1.0/115/70 |
DZL28-1.0/115/70 DZL2.8-1.25/130/70 |
DZL4.2-1.0/115/70 DZL4.2-1.25/130/70 |
||
Rated Capacity T/h | 0.7 | 1.4 | 2.8 | 4.2 | ||
Rated Working Pressure Mpa | 0.7 | 0.7/1.0 | 1.0/1.25 | 1.0/1.25 | ||
Rated Steam Temp. ℃ | 95 | 95/115 | 115/130 | 115/130 | ||
Feed Water Temp. ℃ | 70 | 70 | 70 | 70 | ||
Fuel Consumption Kg/H | ~150 | ~310 | ~590 | ~900 | ||
Thermal Efficiency % | 75 | 78 | 79 | 77.44 | ||
Heating Surface | Boiler Body m² | 32.4 | 33.85 | 75.75 | 142 | |
Economizer m² | 24.64 | 38.5 | 87.2 | |||
Grate area m² | 1.4/2.05 | 2.3/3.5 | 4.66 | 7.4 | ||
Designed Fuel Type | Bituminous Coal | Bituminous Coal | Bituminous Coal | Bituminous Coal | ||
Max. Transport Weight T | ~16 | ~21 | ~26.5 | ~30 | ||
Max. Transport Dimension m | 4.3×2.25×2.955.26×2.25×2.95 | 5.1×2.2×3.35.9×2.2×3.3 | 6.5×2.6×3.5 | 6.01×3.4×3.57.29×2.9×1.7 | ||
Boiler Auxiliary Equipment Model and Specification | ||||||
Air Blower | Model | T4-72-11;3.2A Right | T4-72-11;3.5A Right | T4-72-11;4A Right | T4-72-11;5A Right | |
Motor Power | N=1.5 Kw | N=3 Kw | N=5.5 Kw | N=11 Kw | ||
Draft Fan | Model | YX9-355C ; Right 0° | Y-9-26;6.3C ; Right 0° | Y-9-26;9D;Right 0° | Y8-399D;Ring 0° | |
Motor Power | N=5.5 Kw | N=11 Kw | N=22 Kw | N=30 Kw | ||
Gear Box | Model | GL-5P | GL-5P | GL-5P | GL-10P | |
Motor Power | N=0.55 Kw | N=0.55 Kw | N=0.55 Kw | N=1.1Kw | ||
Feed Water Pump | Model | 1.5WCT-120 | 1.5WCT-120 | 1½ GC5x5 | 2GC5x4 | |
Motor Power | N=2.2 Kw | N=2.2Kw | N=5.5 Kw | N=11 Kw | ||
Dust Remover | Model | XD-1 | XD-2 | XD-4 | XD-6 |
ModelItem | DZL7-1.0/115/70 | DZL14-1.0/115/70 | DZL29-1.25/130/70 | DZL46-1.25/130/70 | DZL58-1.25/130/70 | DZL70-1.25/130/70 | |
Rated Capacity T/h | 7 | 14 | 29 | 46 | 58 | 70 | |
Rated Working Pressure Mpa | 1.0 | 1.0 | 1.25 | 1.25 | 1.25 | 1.25 | |
Rated Steam Temp. ℃ | 115 | 115 | 130 | 130 | 130 | 130 | |
Feed Water Temp. ℃ | 70 | 70 | 70 | 70 | 70 | 70 | |
Heating AreaBoiler Body m² | 228.6 | 434.7 | Radiation:73.07Convection:903.01 | Radiation:147.8Convection:1418.5 | Radiation:147.8Convection:1418.5 | Radiation:147.8Convection:1418.5 | |
Grate area m² | 11.5 | 22.5 | 34.5 | 57.8 | 77 | 91 | |
FuelKj/Kg | Coal | Class II Bituminous Coal | |||||
Low heat | 18757 | 17693 | |||||
Fuel Consumption Kg/h | ~1440 | ~2700 | ~6610 | ~10500 | ~12800 | ~15300 | |
Thermal Efficiency % | 80 | 80 | 82.5 | 82.05 | 83.03 | 83.28 | |
Max. Transport Weight Ton | 35 | 28 | 19.68 | 28.796 | 31 | 31 |
Product detail pictures:
Related Product Guide:
Boiler Structure
With our abundant experience and considerate products and services, we have been recognized to be a reputable supplier for a lot of global consumers for Electric Boiler Industry - Single Drum Hot Water Boiler – Double Rings , The product will supply to all over the world, such as: belarus, Anguilla, Greece, We are trying our best to make more customers happy and satisfied. we sincerely hope to establish a good long-term business relationship with your esteemed company thought this opportunity,based on equal, mutual beneficial and win win business from now till the future.